AC digital output, 12 channels,
- In stock 1
Opto 22 GRV-OACIS-12 12-250 VAC Output Module - Complete Specification Sheet
1. Basic Product Information
表格
| Item | Detailed Specification |
|---|---|
| Part Number | GRV-OACIS-12 |
| Product Series | groov 12–250 VAC Output Modules |
| Product Category | I/O Modules (groov EPIC® System Compatible) |
| Product Description | AC digital output module, 12 channels, 12–250 VAC, with channel-to-channel isolation and on/off only functionality |
| Core Application | Switching up to 12 separate AC loads; compatible with groov EPIC® (Edge Programmable Industrial Controller) system; ideal for industrial automation, process control, and remote monitoring |
| Key System Integration | Wired directly to field devices (sensors/actuators); translates electrical signals to digital language for local network or cloud data use |
| Status | Active |
| Manufacturer | Opto 22 |
| Factory Testing | Twice before shipment |
| Warranty | Lifetime Guarantee |
2. Core Features
- Channel Configuration: 12 independent channels with channel-to-channel isolation (no shared field signal connections internally)
- Operational Mode: On/off only functionality (cost-effective for simple switching requirements)
- Switching Protection: Zero voltage turn-on and zero current turn-off to minimize transients; 300V transient protection between field signals and logic side
- User Interface: Module cover with LED (module health indicator) and touch-sensitive pad (triggers module info display on groov EPIC® processor)
- Mechanical Design: Swinging two-position cover (accommodates thick wires) with dead-front design; top-mounted removable spring-clamp terminal connector
- Installation Flexibility: Hot-swappable (install/remove without powering down); self-identifying (auto-communicates with chassis upon mounting)
- Environmental Suitability: UL Hazardous Locations approved and ATEX compliant
3. Electrical Specifications
表格
| Parameter | Rating | Notes |
|---|---|---|
| Line Voltage Range | 12–250 VAC | Operating voltage for connected AC loads |
| Current Rating (per channel) | 0.5 A | Maximum current per channel |
| Minimum Load Current | 20 mA | Required minimum load for stable operation |
| Output Voltage Drop | 1 V | Voltage drop when channel is active |
| Off-state Leakage Current (60 Hz) | 1.25 mA @ 240 VAC; 0.7 mA @ 120 VAC | Leakage at nominal voltage |
| Peak Blocking Voltage | 500 V | Maximum blocking voltage capability |
| Operating Frequency | 40 to 60 Hz, 400 Hz | Compatible AC frequency ranges |
| Turn-on Time | ≤ 1/2 cycle (zero crossing) | Zero voltage switching |
| Turn-off Time | ≤ 1/2 cycle (zero crossing) | Zero current switching |
| TPO Period | N/A | Not supported (on/off only functionality) |
| Isolation (Field-to-Logic) | 300 V working; 1500 V transient (1 minute) | Protection between field and logic circuits |
| Isolation (Channel-to-Channel) | 300 V working | Independent isolation between channels |
| Chassis Power Consumption | 1.3 W | Power drawn from groov EPIC chassis |
| Recommended Over-Current Protection | 2 A 250 VAC per channel; 6 A 250 VAC common | Fast-acting fuse or circuit breaker |
4. Mechanical & Physical Specifications
4.1 Dimensions (Imperial/Metric)
表格
| Dimension | Cover in Lower Position | Cover in Higher Position |
|---|---|---|
| Overall Height | 6.75 in / 171.5 mm | 7.25 in / 184.2 mm |
| Length | 5.42 in / 137.8 mm | 5.92 in / 150.5 mm |
| Width | 0.77 in / 19.4 mm | 0.77 in / 19.4 mm |
| Wireway Height | 5.42 in / 137.8 mm | 6.09 in / 154.8 mm |
4.2 Terminal & Wiring Specifications
表格
| Item | Specification |
|---|---|
| Wire Size | 28–14 AWG |
| Wire Strip Length | 0.315–0.354 inches (8–9 mm) |
| Terminal Type | Spring-clamp terminals |
| Terminal Connector | Removable (held by captive retention screw) |
| Connector Screw Torque | 2.5 in-lb (0.28 N-m) |
| Hold-down Screw Torque | 3.5 in-lb (0.4 N-m) |
| Wiring Tool Requirements | Flathead screwdriver (2.5 mm x 0.4 mm tip) or groov spring-clamp terminal tool (GRVTEX-SCTOOL) |
4.3 Environmental Ratings
表格
| Parameter | Range |
|---|---|
| Operating Temperature | -20 °C to +70 °C |
| Storage Temperature | -40 °C to +85 °C |
| Relative Humidity (Non-Condensing) | 5–95% |
| MTBF (Minimum, 25 °C) | 1.2 Mhrs |
5. Software & Firmware Requirements
表格
| Requirement | Minimum Version |
|---|---|
| groov EPIC Firmware | 1.0.0 |
| PAC Project | 10.0000 |
| CODESYS Library Package | 1.0.0.0 |
6. Agency Approvals & Compliance
表格
| Standard | Status/Details |
|---|---|
| UL/cUL | Listed (Class 1, Div 2) |
| CE Directives | ATEX (Category 3, Zone 2), Low Voltage, EMC |
| RoHS | Compliant |
| DFARS | Compliant |
| CB Scheme | Compliant |
| UKCA | Compliant |
| Note for Hazardous Locations | Must be mounted in an enclosure meeting National Electrical Code (ANSI/NFPA 70) and ANSI/ISA-61010-1 (82.02.01) requirements |
7. Pinout & Wiring Instructions
7.1 Key Wiring Notes
- All loads require user-supplied fuses (per over-current protection specs)
- Channels are isolated; no shared field connections
- Terminal connector features clamp release holes and field wiring holes for spring-clamp operation
7.2 Channel Pinout (Internal Pin → External Wiring)
表格
| Channel | Internal Pins | External Connection |
|---|---|---|
| Channel 0 | 2, 3 | AC Load (Line or Common) |
| Channel 1 | 4, 5 | AC Load (Line) |
| Channel 2 | 6, 7 | AC Load (Line) |
| Channel 3 | 8, 9 | AC Load |
| Channel 4 | 10, 11 | AC Load (Line) |
| Channel 5 | 12, 13 | AC Load (Line) |
| Channel 6 | 15, 16 | AC Load (Line or Common) |
| Channel 7 | 17, 18 | AC Load |
| Channel 8 | 19, 20 | AC Load (Line) |
| Channel 9 | 21, 22 | AC Load (Line) |
| Channel 10 | 23, 24 | AC Load (Line) |
| Channel 11 | 25, 26 | AC Load (Line) |
| Unused Pins | 14 | No connection |
7.3 Wiring Procedures
Inserting Wires
- Orient module/terminal connector to match wiring diagram.
- Secure module or terminal connector (clamp if detached).
- Insert tool into clamp release hole (press against side furthest from terminal numbers) and press straight down until bottom is reached.
- Insert stripped wire into field wiring hole.
- Pull out tool to engage spring clamp.
- Test wire security by gentle tugging.
Removing Wires
- Insert tool into clamp release hole and press straight down.
- Pull wire out of field wiring hole.
- Remove tool to reset spring clamp.
8. Mounting & Unmounting Instructions
8.1 Mounting Steps
- De-energize field devices connected to the terminal connector.
- Orient groov EPIC chassis with module connector numbers right-side up (0 on left).
- Hold module at 45° angle, align alignment tab with chassis slot.
- Pivot module down to snap into chassis connector.
- Lift module cover, tighten hold-down screw (3.5 in-lb torque).
- Install terminal connector (if not pre-installed) and tighten connector screw (2.5 in-lb torque).
- Wire field devices per pinout instructions.
- Close module cover (adjust to higher position for thick wires if needed).
- Restore power (if previously powered down).
8.2 Unmounting Steps
- De-energize field devices connected to the terminal connector.
- Lift module cover to access wiring and hold-down screw.
- Remove wiring:
- Remove hold-down screw.
- Pull up on module grip tab to release from chassis connector, then remove module.
- Restore power (if applicable).
9. Module Parts & Functions
表格
| Part Name | Function |
|---|---|
| Module LED | Indicates module health (e.g., solid blue = normal; blinking blue = info displayed on EPIC processor) |
| Touch-sensitive Pad | Triggers module info (specs, wiring diagram) on groov EPIC processor (press for ~2 seconds) |
| Two-position Hinge | Adjusts cover height for wire clearance |
| Wireway | Space under cover for wiring; expanded with higher hinge position |
| Catch Tab | Secures cover in open position for wiring access |
| Strain Relief Tab | Secures wire bundles (via zip tie) to prevent strain on terminals |
| Alignment Tab | Guides module into chassis slot during mounting |
| Module Grip Tab | Facilitates module removal from chassis |
| Discrete Channel Indicators | Displays on/off status of each channel |
Purchase
No need to register to order from JMChip Electronics, but signing in lets you track your order like a pro. Give it a try for a smoother shopping ride.
Means
Easy peasy! Pay your way with PayPal, Credit Card, or wire transfer in USD. We've got you covered.
RFQ(Request for Quotations)
Get the freshest prices and stock updates by asking for a quote! Our sales team will shoot you an email within a day. It's that simple.
IMPORTANT NOTICE
1. Look out for your order details in your inbox! (If it's missing, check the spam folder just in case.)
2. Our sales manager will double-check the order and keep you posted on any price or stock changes. No worries, we've got you covered.

Shipping Rate
We ship orders once a day around 5 p.m., except Sunday. Once shipped, the estimated delivery time depends on the courier company you choose, usually 5-7 working days.

Shipping Methods
We provide DHL, FedEx, UPS, EMS, SF Express, and Registered Air Mail international shipping.


Payment
You can pay the orders on the website directly or pay by wire transfer offline. We support: Paypal、VISA、Credit Card.